3-91 Ramp Time
Range: Function:
1.00 s [0.00 - 3600.00 s] Enter the ramp time, i.e. the time for adjustment of the reference from 0% to 100% of the specified
digital potentiometer function (INCREASE, DECREASE or CLEAR).
If INCREASE / DECREASE is activated for longer than the ramp delay period specified in par.
3-95
Ramp Delay
the actual reference will be ramped up / down according to this ramp time. The
ramp time is defined as the time used to adjust the reference by the step size specified in par.
3-90
Step Size
.
3-92 Power Restore
Option: Function:
[0] * Off Resets the Digital Potentiometer reference to 0% after power up.
[1] On Restores the most recent Digital Potentiometer reference at power up.
3-93 Maximum Limit
Range: Function:
100 %* [-200 - 200 %] Set the maximum permissible value for the resultant reference. This is advisable if the Digital Po-
tentiometer is used for fine tuning of the resulting reference.
3-94 Minimum Limit
Range: Function:
0 %* [-200 - 200 %] Set the minimum permissible value for the resultant reference. This is advisable if the Digital Po-
tentiometer is used for fine tuning of the resulting reference.
3-95 Ramp Delay
Range: Function:
1.000 N/A* [0.000 - 3600.000 N/A]
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
63