8-32 Baud Rate
Option: Function:
Baud rate selection depends on Protocol selection in par. 8-30
Protocol
.
[0] 2400 Baud
[1] 4800 Baud
[2] * 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol par. 8-30
Protocol
using the FC Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
[0] * Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range: Function:
10. ms* [5. - 10000. ms] Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
8-36 Maximum Response Delay
Range: Function:
Application
Depend-
ent*
[11. - 10001. ms] Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word time-out.
8-37 Maximum Inter-Char Delay
Range: Function:
25.00 ms* [0.00 - 35.00 ms] Specify the maximum permissible time interval between receipt of two bytes. This parameter acti-
vates time-out if transmission is interrupted.
8-40 Telegram Selection
Option: Function:
Enables use of freely configurable telegrams or standard telegrams for the FC port.
[1] * Standard telegram 1
[200] Custom telegram 1
8-45 BTM Transaction Command
Option: Function:
[0] * Off
[1] Start Transaction
[2] Commit transaction
[3] Clear error