8-46 BTM Transaction Status
Option: Function:
[0] * Off
[1] Transaction Started
[2] Transaction Comitting
[3] Transaction Timeout
[4] Err. Non-existing Par.
[5] Err. Par. Out of Range
8-47 BTM Timeout
Range: Function:
60 s* [0 - 360 s]
3.9.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
99