User Guide | Controller for appliance control, AK-CC 450
RS8EU702 | 27
© Danfoss | ADAP-KOOL® | 2015.10
Case Room
Defrost stop on
time
Defrost stop
on S5
Defrost stop on
time
Defrost stop
on S5
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP)
2°C -2°C -28°C 4°C 0°C -22°C
Max. temp. setting (r02)
6°C 4°C -22°C 8°C 5°C -20°C
Min. temp. setting (r03)
0°C -4°C -30°C 0°C -2°C -24°C
Sensor signal for thermostat. S4% (r15)
100% 0%
Alarm limit high (A13)
8°C 6°C -15°C 10°C 8°C -15°C
Alarm limit low (A14)
-5°C -5°C -30°C 0°C 0°C -30°C
Sensor signal for alarm funct.S4% (A36)
0% 100% 0%
Interval between defrost (d03)
6 h 6h 12h 8h 8h 6h
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
0 1 1 0 1 1
DI1 cong. (o02)
Case cleaning (=10) Door function (=2)
Sensor signal for display view S4% (017)
0%
Note: For applications 6 and 7 the sensor weighting for the S3/S4 sensors is not used for the thermostat, alarm thermostat and display readings as the
sensor uses are predened.