User Guide | Controller for appliance control, AK-CC 450
© Danfoss | ADAP-KOOL® | 2015.10
30 | RS8EU702 |
Network address (0= o)
o03 1 1 1 1 1 1 1 1 1 0 240 0
On/O switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at LON 485 only and DANBUSS)
o04 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Access code 1 (all settings)
o05 1 1 1 1 1 1 1 1 1 0 100 0
Used sensor type : 0=Pt1000, 1=Ptc1000,
o06 1 1 1 1 1 1 1 1 1 0/Pt 1/Ptc 0/Pt
Software Version
o08 1 1 1 1 1 1 1 1 1 100 999
Max hold time after coordinated defrost
o16 1 1 1 1 1 1 1 1 1 0 min. 360 min. 20
Select signal for display view. S4% (100%=S4, 0%=S3)
o17 1 1 1 1 1 0 % 100 % 100
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start (pulse-
signal). 5=ext. main switch 6=night operation 7=Thermostat
band changeover (activate r21). 8=alarm function when
closed. 9=alarm function when open. 10=case cleaning (pulse
signal). 11=forced cooling at hot gas defrost.). 12=night cover,
13=coordinated defrost). 15=application shutdown
o37 1 1 1 1 1 1 1 1 1 0 15 0
Conguration of light function: 1=Light follows day /night
operation, 2=Light control via data communication via
o39’, 3=Light control with a DI-input, 4=As "2", but light
switch on and night cover will open if the network cut out
for more than 15 minutes.
o38 1 1 1 1 1 1 1 1 1 1 4 1
Activation of light relay (only if o38=2) On=light
o39 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Rail heat On time during day operations
o41 1 1 1 1 0 % 100 % 100
Rail heat On time during night operations
o42 1 1 1 1 0 % 100 % 100
Rail heat period time (On time + O time)
o43 1 1 1 1 6 min. 60 min. 10
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output
O.
*** o46 1 1 1 1 1 1 1 1 1 0 2 0
Selection of EL diagram. See overview page 12 and 13
* o61 1 1 1 1 1 1 1 1 1 1 8 1
Download a set of predetermined settings. See overview page
27
* o62 1 1 1 1 1 1 1 1 1 0 6 0
Access code 2 (partial access)
*** o64 1 1 1 1 1 1 1 1 1 0 100 0
Replace the controllers factory settings with the present set-
tings
o67 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Input signal on DI3. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start (pulse-
signal). 5=ext. main switch 6=night operation, 7=Thermostat
band changeover (activate r21). 8=Not used. 9=Not used.
10=case cleaning (pulse signal). 11=forced cooling at hot gas
defrost, 12=night cover. 13=Not used. 14=Refrigeration
stopped (forced closing)). 15= application shutdown
o84 1 1 1 1 1 1 1 1 1 0 15 0
Rail heat control
0=not used, 1=pulse control with timer function (o41 and
o42), 2=pulse control with dew point function
o85 1 1 1 1 0 2 0
Dew point value where the rail heat is minimum
o86 1 1 1 1 -10°C 50°C 8
Dew point value where the rail heat is 100% on
o87 1 1 1 1 -9°C 50°C 17
Lowest permitted rail heat eect in %
o88 1 1 1 1 0 % 100 % 30
Time delay from "open door refrigeration is started
o89 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Fan operation on stopped refrigeration (forced closing):
0 = Stopped (defrosting permitted)
1= Running (defrosting permitted)
2=Stopped (defrosting not permitted)
3= Running (defrosting not permitted)
o90 1 1 1 1 1 1 1 1 1 0 3 1
Denition of readings on lower button:
1=defrost stop temperature, 2=S6 temperature, 3=S5_B
temperature. 4= Readout of S3B temperature
o92 1 1 1 1 1 1 1 1 1 1 4 1
Display of temperature
1= u56 Air temperature
2= u36 product temperature
o97 1 1 1 1 1 1 1 1 1 1 2 1
Light and night blinds dened
0: Light is switch o and night blind is open when the
main switch is o
1: Light and night blind is independent of main switch
o98 1 1 1 1 1 1 1 1 1 0 1 0
Continued Code 1 2 3 4 5 6 7 8 9 Min. Max. Fac. Actual

Table of Contents