EasyManua.ls Logo

Danfoss AK-CC 550A - Menu survey - Part 3

Danfoss AK-CC 550A
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 Manual RS8FS402 © Danfoss 2016-03 AK-CC 550A
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation
7=thermostat band changeover (activate r21). 8=alarm
function when closed. 9=alarm function when open.
10=Appliance cleaning (pulse signal). 11=forced cooling at
hot gas defrost.). 12=night cover, 13=coordinated defrost).
15=case shut down
o37 1 1 1 1 1 1 1 1 1 1 0 15 0
Conguration of light function: 1=Light follows day /night
operation, 2=Light control via data communication
via o39’, 3=Light control with a DI-input, 4=As "2", but
light switch on and night cover will open if the network
cut out for more than 15 minutes.
o38 1 1 1 1 1 1 1 1 1 4 1
Activation of light relay (only if o38=2) On=light o39 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Rail heat On time during day operations
o41 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat On time during night operations
o42 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat period time (On time + O time)
o43 1 1 1 1 1 1 1 6 min. 60 min. 10
Appliance cleaning. 0=no Appliance cleaning. 1=Fans only.
2=All output O.
*** o46 1 1 1 1 1 1 1 1 1 1 0 2 0
Selection of EL diagram. See overview page 12 and 13
* o61 1 1 1 1 1 1 1 1 1 1 1 10 1
Download a set of predetermined settings. See overview
page 27.
* o62 1 1 1 1 1 1 1 1 1 1 0 6 0
Access code 2 (partial access)
*** o64 1 1 1 1 1 1 1 1 1 1 0 100 0
Replace the controllers factory settings with the present
settings
o67 1 1 1 1 1 1 1 1 1 1 0/O 1/On 0/O
Input signal on DI3. Function: (high voltage input)
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse-signal). 5=ext. main switch 6=night operation,
7=thermostat band changeover (activate r21). 8=Not
used. 9=Not used. 10=Appliance cleaning (pulse signal).
11=forced cooling at hot gas defrost, 12=night cover.
13=Not used. 14=Refrigeration stopped (forced
closing)). 15=case shut down
o84 1 1 1 1 1 1 1 1 1 1 0 15 0
Rail heat control
0=not used, 1=pulse control with timer function (o41
and o42), 2=pulse control with dew point function
o85 1 1 1 1 1 1 1 0 2 0
Dew point value where the rail heat is minimum o86 1 1 1 1 1 1 1 -10°C 50°C 8
Dew point value where the rail heat is 100% on o87 1 1 1 1 1 1 1 -9°C 50°C 17
Lowest permitted rail heat eect in % o88 1 1 1 1 1 1 1 0 % 100 % 30
Time delay from "open door refrigeration is started o89 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Fan operation at stopped cooling (forced closing):
0= Stopped (defrost allowed)
1= Running (defrost allowed)
2= Stopped (defrost not allowed)
3= Running (defrost not allowed)
o90 1 1 1 1 1 1 1 1 1 1
0 3 1
1=defrost stop temperature, 2=S6 temperature,
3=S5_B temperature (application 9), 4=S3B (application
10)
o92 1 1 1 1 1 1 1 1 1 1 1 4 1
Display of temperature
1= u56 Air temperature
2= u36 product temperature
o97 1 1 1 1 1 1 1 1 1 1 1 2 1
Light and night blinds dened
0: Light is switch o and night blind is open when the
main switch is o
1: Light and night blind is independent of main switch
o98 1 1 1 1 1 1 1 1 1 1 0 1 0
Conguration of alarm relay
The alarm relay will be activated upon an alarm signal
from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
The groups that are to activate the alarm relay must be
set by using a numerical value which is the sum of the
groups that must be activated.
(E.g.: a value of 5 will activate all high temperature
alarms and all sensor error and 0 will cancel the relay
function).
P41 1 1 1 1 1 0 127 111

Other manuals for Danfoss AK-CC 550A

Related product manuals