N O T I C E
This option is available only with software version 48.XX.
The virtual master is running on the set reference.
N O T I C E
This option is only available in FC 302.
N O T I C E
This option is only available in FC 302.
N O T I C E
This option is only available in FC 302.
The drive has been operating in emergency mode.
The drive is operating in emergency mode. See parameter group 24-0* Emergency Mode.
Emergency mode is not operating as expected, for example, live zero monitoring on an analog
input is activated.
During emergency mode operation, 1 of the critical alarms has been activated and suppressed
by emergency mode. This may lead to reduced drive performance and expected lifetime before
service is required.
Emergency mode was activated in a special test mode where the drive stops on all alarms.
Parameter 5-41 On Delay, Relay
Table 362: Parameter 5-41 On Delay, Relay
Parameter type: Range, 0.01 – 600 s, Array [9]
Change during operation: True
Enter the delay of the relay cut in time. Select 1 of 2 internal mechanical relays in an array function. See parameter 5-40 Function
Relay for details.
AU275636650261en-000101 / 130R0334216 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide