Setting the time delay to pass from the drive experiences an alarm that stops it and until the motor is automatically switched to
bypass control. If the delay is set to 0, a drive alarm does not automatically switch the motor to bypass control.
Parameter 31-03 Test Mode Activation
Table 1107: Parameter 31-03 Test Mode Activation
31-03 Test Mode Activation
Default value: [0] Disabled
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Disabled
Test mode is disabled.
[1]
Enabled
The motor runs in bypass while the drive can be tested into an open circuit. In this mode, keypad does not
control start/stop of bypass.
Parameter 31-10 Bypass Status Word
Table 1108: Parameter 31-10 Bypass Status Word
31-10 Bypass Status Word
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 74
Data type: V2
Change during operation: False
View the status of the bypass as a hexadecimal value.
Parameter 31-11 Bypass Running Hours
Table 1109: Parameter 31-11 Bypass Running Hours
31-11 Bypass Running Hours
Default value: 0 h
Parameter type: Range, 0 - 2147483647 h
Setup: All setups
Conversion index: 74
Data type: Uint32
Change during operation: False
View the number of hours in which the motor has run in bypass mode. The counter can be reset in parameter 15-07 Reset Running
Hours Counter. The value is saved when the drive is turned off.
Parameter 31-19 Remote Bypass Activation
Table 1110: Parameter 31-19 Remote Bypass Activation
31-19 Remote Bypass Activation
Default value: [0] Disabled
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Disabled
[1]
Enabled
5.25 Parameter Group 32-** MCO Basic Settings
Parameters in this group are available when VLT® Motion Control Option MCO 305 is installed in the drive. For information about
the option, see the VLT® MCO Control Option MCO 305 Operating Guide.
AU275636650261en-000101 / 130R0334 | 587Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss D9h

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss D9h and is the answer not in the manual?

Danfoss D9h Specifications

General IconGeneral
BrandDanfoss
ModelD9h
CategoryDC Drives
LanguageEnglish

Related product manuals