5.16.5 16-6* Inputs and Outputs
N O T I C E
The following parameters are only available in FC 302:
Parameter 16-67 Freq. Input #29 [Hz]
Parameter 16-70 Pulse Output #29 [Hz]
Parameter 16-60 Digital Input
Table 873: Parameter 16-60 Digital Input
Parameter type: Range, 0 - 65535
Change during operation: False
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit number 5, 0 = no signal, 1 = connected
signal. Bit 6 works in the opposite way, on = 0, off = 1 (Safe Torque Off input).
Table 874: Active Digital Inputs
Digital input terminal 33.
Digital input terminal 32.
Digital input terminal 29.
Digital input terminal 27.
Digital input terminal 19.
Digital input terminal 18.
Digital input terminal 37.
Digital input VLT® General Purpose I/O MCB 101 terminal X30/4.
Digital input VLT® General Purpose I/O MCB 101 terminal X30/3.
Digital input VLT® General Purpose I/O MCB 101 terminal X30/2.
Reserved for future terminals.
AU275636650261en-000101 / 130R0334 | 507Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide