Parameter 0-31 Min Value of User-defined Readout
Table 22: Parameter 0-31 Min Value of User-defined Readout
0-31 Min Value of User-defined Readout
Default value: 0 CustomReadoutUnit
Parameter type: Range, -999999.99 CustomReadoutUnit
- par. 0-32
Change during operation: True
This parameter sets the minimum value of the custom-defined readout (occurs at 0 speed). Only possible to set different from 0
when selecting a linear unit in parameter 0-30 Unit for User-defined Readout. For quadratic and cubic units, the minimum value is 0.
Parameter 0-32 Max Value of User-defined Readout
Table 23: Parameter 0-32 Max Value of User-defined Readout
0-32 Max Value of User-defined Readout
Default value: 100 CustomReadoutUnit
Parameter type: Range, par. 0-31 -999999.99 Custom-
ReadoutUnit
Change during operation: True
This parameter sets the maximum value to be shown when the speed of the motor has reached the set value for parameter 4-13
Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz] (depends on setting in parameter 0-02 Motor Speed Unit).
AU275636650261en-000101 / 130R033452 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide