Questions and Answers

  • L
    Lori JonesSep 16, 2025
    How to fix brake resistor short circuit in Danfoss D9h?
    • K
      kwigginsSep 16, 2025
      If your Danfoss DC Drives are reporting a brake resistor short circuit, the brake resistor is being monitored during operation. Remove the power to the frequency converter and replace the brake resistor.
  • P
    Patricia ClarkSep 16, 2025
    What does 'Motor mod. changed' mean on Danfoss D9h DC Drives?
    • C
      Christopher WrightSep 16, 2025
      If your Danfoss DC Drives display 'Motor mod. changed', it means the motor selected in parameter 1-11 Motor Model is not correct. Check the motor model.
  • S
    stephanie22Sep 16, 2025
    What does 'Ext. supply' mean on Danfoss D9h DC Drives?
    • G
      gregorykevinSep 16, 2025
      If your Danfoss DC Drives display an 'Ext. supply' error, it means the VLT[®] Extended Relay Option MCB 113 is mounted without external 24 V DC. Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC.
  • M
    Margaret NelsonSep 16, 2025
    How to troubleshoot a live zero error on Danfoss DC Drives?
    • S
      Stephanie GonzalesSep 17, 2025
      If you're encountering a live zero error with your Danfoss DC Drives, it could be due to broken wiring or a faulty device sending the signal. Check connections on all analog mains terminals.
  • J
    Jamie BrownSep 17, 2025
    What to do if control card voltage is less than 10 V in Danfoss DC Drives?
    • M
      Michael MooreSep 18, 2025
      If the control card voltage is less than 10 V in your Danfoss DC Drives, remove some of the load from terminal 50, as the 10 V supply is overloaded. The maximum load should be 15 mA or a minimum of 590 ?.
  • M
    Melissa PerezSep 18, 2025
    What does it mean if the brake check failed on Danfoss D9h?
    • C
      Christopher MillerSep 18, 2025
      If the brake check failed on your Danfoss DC Drives, it means the brake resistor is not connected or not working. Check parameter 2-15 Brake Check.
  • M
    Maria RandolphSep 18, 2025
    What to do if motor phase U is missing in Danfoss D9h DC Drives?
    • S
      Stephen ScottSep 18, 2025
      If your Danfoss DC Drives report that motor phase U is missing, remove the power from the frequency converter and check motor phase U.
  • E
    Emily JacksonSep 18, 2025
    What to do if motor phase V is missing in Danfoss DC Drives?
    • L
      Lisa MelendezSep 18, 2025
      If your Danfoss DC Drives report that motor phase V is missing, remove the power from the frequency converter and check motor phase V.
  • K
    Kelly DaviesSep 18, 2025
    What to do if motor phase W is missing in Danfoss D9h?
    • L
      Laura WellsSep 18, 2025
      If your Danfoss DC Drives report that motor phase W is missing, remove the power from the frequency converter and check motor phase W.
  • B
    brownjenniferSep 18, 2025
    What to do if Danfoss D9h DC Drives show over current?
    • N
      Nicole EllisSep 18, 2025
      If your Danfoss DC drive shows an over current error, it means the inverter peak current limit (approximately 200% of the rated current) is exceeded. You should remove power and check if the motor shaft can be turned. Also, check that the motor size matches the frequency converter and verify parameters 1-20 through 1-25 for correct motor data.