GENERAL INFORMATIONPRODUCT INFORMATIONINTEGRATION INTO SYSTEMORDERING INFORMATION SYSTEM DESIGN
Reduce moisture in the system
Excessive air and moisture
can increase condensing pressure and cause
high discharge temperatures.
can create acid giving rise to copper platting.
can destroy the lubricating properties of the oil.
All these phenomena can reduce service life
and cause mechanical and electrical compressor
failure.
Requirements
Solutions
DSH compressors are delivered with < 100ppm
moisture level.
At the time of commissioning, system moisture
content may be up to 100ppm.
During operation, the filter drier must reduce this
to a level between 20 and 50ppm.
To achieve this requirement, a properly sized
and type of drier is required. Important selection
criterias include:
driers water content capacity,
system refrigeration capacity,
system refrigerant charge.
For new installations with DSH compressors with
polyolester oil, Danfoss recommends using the
Danfoss DML (100% molecular sieve) solid core
filter drier.
R
49FRCC.PC.045.A7.02

Table of Contents

Other manuals for Danfoss DSH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DSH Series and is the answer not in the manual?

Danfoss DSH Series Specifications

General IconGeneral
BrandDanfoss
ModelDSH Series
CategoryAir Compressor
LanguageEnglish

Related product manuals