Installation
14c
Connecting the room panel / remote control
The ECA 60 / 61 / 62 / 63 is activated by the setting in line 10 
(section 32). 
The ECA 60 / 61 / 62 / 63 is powered by the system device bus 
which means that the bus must be active. The bus is activated by 
setting the controller address to 15 (section 32, line 199).
Override
For an active override, you have to choose the mode 
“scheduled operation”! Input S1 ... S6 (ECL Card C14 only uses 
S5) can be used for override purposes (section 32, line 141).
Connection example without ECA 9010
If the override switch has goldplated contacts, you can 
choose one of the following solutions or a combination of 
both:
(C14 = 21 only)  (C14 = 21 only)
Closed switch:   Closed switch: 
Comfort temperature   Setback temperature
Open switch:  Open switch: 
Scheduled operation  Scheduled operation
Connection example with ECA 9010
The ECA 9010 module is powered by the system device bus, 
which means that the bus must be active. The bus is activated 
by setting the controller address to 15 (line 199). To avoid 
inuence from contact resistance, the use of ECA 9010 is 
recommended. 
Comfort  Setback
Red
Brown
Green S1 ... S6 (C14 = S5 only)