Return temp.
(S4)
Push and hold the shift button to see:
- the calculated ow temperature
- the desired return temperature limitation.
The activity of the motorized control valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display will
indicate it as “- -”.
If the sensor is short-circuited, the display will indicate
it as “- - -“.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value