The grey
side of the
ECL Card
Basic set-up
Room temperature inuence -
line 3
23a
This section is only relevant if you have installed a room
temperature sensor or ECA 60 / ECA 61 / ECA 62 / ECA 63.
Min.
inuence
1
2
ON
0-4
0
3
1
ON
3
ON
Max.
inuence
3 Room temperature inuence
Circuit Setting range Factory setting
I 0 ... 99 / -99 ... 0 min. 0, max. -40
The bar below the min. value blinks. Adjust the
min. inuence.
Select the max. inuence.
The bar below the max. value blinks.
Adjust the max. inuence.
There are two basic principles for control of the room
temperature inuence:
A: Max. room temperature limitation
Use this limitation if your system is fully equipped with
thermostats and you also want to obtain a max. limitation of
the room temperature. The controller will allow for free heat
gains, i.e. solar radiation or heat from a re place, etc.
Inuence
Desired room
temperature
Room
temperature
Max.
limitation
The max. inuence determines how much the room
temperature should inuence the desired ow temperature.
Example
The actual room temperature is 2 degrees too high.
The inuence at max. limitation (right corner of the display) is
set to -40.
The inuence at min. limitation (left corner of the display) is set
to 0.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x -40 x 1.8 x 0.1 = -14.4 degrees.