The grey
side of the
ECL Card
Basic set-up
Room temperature inuence -
line 3
23a
This section is only relevant if you have installed a room
temperature sensor or ECA 60 / ECA 61 / ECA 62 / ECA 63.
Min.
inuence
Max.
inuence
3 Room temperature inuence
Circuit Setting range Factory setting
I 0 ... 99 / -99 ... 0 min. 0, max. -40
The bar below the min. value blinks. Adjust the
min. inuence.
Select the max. inuence.
The bar below the max. value blinks.
Adjust the max. inuence.
There are two basic principles for control of the room
temperature inuence:
A: Max. room temperature limitation
Use this limitation if your system is fully equipped with
thermostats and you also want to obtain a max. limitation of
the room temperature. The controller will allow for free heat
gains, i.e. solar radiation or heat from a re place, etc.
Inuence
Desired room
temperature
Room
temperature
Max.
limitation
The max. inuence determines how much the room
temperature should inuence the desired ow temperature.
Example
The actual room temperature is 2 degrees too high.
The inuence at max. limitation (right corner of the display) is
set to -40.
The inuence at min. limitation (left corner of the display) is set
to 0.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x -40 x 1.8 x 0.1 = -14.4 degrees.