The grey
side of the 
ECL Card
Basic set-up
23b
B: Reference room temperature control
Used if your system is not equipped with thermostats and 
you select the room with room temperature sensor as a
temperature reference for the rest of the rooms.
Set a positive value for the min. inuence and a negative 
value for the max. inuence.
The room temperature sensor in the reference room registers 
the dierence between the desired and the actual room 
temperature. The desired ow temperature will be corrected 
to eliminate this dierence.
Example 1
The actual room temperature is 2 degrees too low.
The inuence at max. limitation (right corner of the display) is
set to -35.
The inuence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x 20 x 1.8 x 0.1 = 7.2 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The inuence at max. limitation (right corner of the display) is
set to -35.
The inuence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x (-35) x 1.8 x 0.1 = -12.6 degrees.
           Inuence
      Min. limitation
 
        Desired room
        temperature 
                        Room
                        temperature
     
     
                 Max. limitation