EasyManua.ls Logo

Danfoss ECL Comfort 300 - Page 29

Danfoss ECL Comfort 300
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The grey
side of the
ECL Card
Basic set-up
23b
B: Reference room temperature control
Used if your system is not equipped with thermostats and
you select the room with room temperature sensor as a
temperature reference for the rest of the rooms.
Set a positive value for the min. inuence and a negative
value for the max. inuence.
The room temperature sensor in the reference room registers
the dierence between the desired and the actual room
temperature. The desired ow temperature will be corrected
to eliminate this dierence.
Example 1
The actual room temperature is 2 degrees too low.
The inuence at max. limitation (right corner of the display) is
set to -35.
The inuence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x 20 x 1.8 x 0.1 = 7.2 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The inuence at max. limitation (right corner of the display) is
set to -35.
The inuence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired ow temperature is changed by
2 x (-35) x 1.8 x 0.1 = -12.6 degrees.
Inuence
Min. limitation
Desired room
temperature
Room
temperature
Max. limitation

Other manuals for Danfoss ECL Comfort 300

Related product manuals