The grey
side of the
ECL Card
Extended service
32b
Service parameter(s) 12-13
12 Boost
Circuit Setting range Factory setting
I 0 ... 99% 0%
Shortens the heating-up period by increasing the desired ow
temperature by the percentage you set.
Set the percentage at which you want the desired
ow temperature increased temporarily.
In order to shorten the heating-up period after a setback
temperature period, the desired ow temperature can be
increased temporarily (max. 1 hour). At optimizing the boost
is active in the optimization period (line 14).
If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is
connected, the boost stops when the room temperature has
been reached.
The boost also stops at the end of an optimizing period.
13 Reference ramping
Circuit Setting range Factory setting
I 0 ... 99 min. 0 min.
The time in which the desired ow temperature increases slowly
to avoid load peaks in the heat supply.
Set the ramping time for the controller.
Temperature °C
Setting line 13 Time (min.)
In order to avoid load peaks in the supply network, the ow
temperature can be set to increase slowly after a period with
setback temperature. This causes the valve to open slowly.