7b
Humidity, relative
This value (stated in %) refers to the indoor moisture content 
compared to the max. moisture content. The relative humidity 
is measured by the ECA 62 / 63 and is used for the calculation of 
the dew point temperature.
Limitation temperature
Temperature that inuences the desired ow / balance 
temperature.
Pt 1000 sensor
All sensors used with the ECL Comfort controller are based 
on the Pt 1000 type. The resistance is 1000 ohm at 0 °C and it 
changes with 3.9 ohm / degree.
Optimization
The controller optimizes the start time of the scheduled 
temperature periods. Based on the outdoor temperature, the 
controller automatically calculates when to start in order to 
reach the comfort temperature at the set time. The lower the 
outdoor temperature, the earlier the start time. 
Return temperature
The temperature measured in the return inuences the desired 
ow temperature.
Room temperature sensor
Temperature sensor placed in the room (reference room, 
typically the living room) where the temperature is to be 
controlled. 
Room temperature
Temperature measured by the room temperature sensor, room 
panel or remote control. The room temperature can only be 
controlled directly if a sensor is installed. The room temperature 
inuences the desired ow temperature.
Schedule
Schedule for periods with comfort and setback temperatures. 
The schedule can be made individually for each week day and 
may consist of up to 3 comfort periods per day.
Setback temperature
Temperature maintained in the heating / DHW circuit during 
setback temperature periods.
State / mode indicators
White arrow to the left of the symbols (sun / moon). The white 
arrow indicates the present state, comfort (sun) or setback 
(moon), when the controller is in scheduled operation mode. 
The black arrow symbol indicates the mode of the controller.
Time line / bar
Line with numbers representing the hours. Below the time 
line, time bars represent scheduled periods with comfort 
temperature. The bar is divided into half hour sections.
Weather compensation
Flow temperature control based on the outdoor temperature. 
The control is related to a user-dened heat curve.
 
The denitions apply to the Comfort 200 as well as ECL Comfort 
300 series. Consequently, you might come across expressions 
that are not mentioned in your guide.