EasyManuals Logo
Home>Danfoss>Controller>EKE 1C

Danfoss EKE 1C User Manual

Danfoss EKE 1C
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
Label
Parameter
name
Variants
Min
Max
Default
Unit
Modbus
PNU
Can In‐
dex
Can Sub‐
index
Enumeration
CAN/MODBus
G001
Controller
address
1
127
0
3167
550C
5E
G005
Modbus
baudrate
1B, 1C
0
8
0
3170
550C
61
0 = 0 | 1 = 1200 | 2 =
2400 | 3 = 4800 | 4 =
9600 | 5 = 14400 | 6 =
19200 | 7 = 28800 | 8 =
38400
G008
Modbus
mode
1B, 1C
0
2
0
3171
550C
62
0 = 8N1 | 1 = 8E1 | 2 =
8N2
G007
Modbus
mapping
1B, 1C
0
1
0
3172
550C
63
0 = Operation | 1 = Con-
guration
G002
CANbus
baudrate
0
5
0
3173
550C
64
0 = 20k | 1 = 50k | 2 =
125k | 3 = 250k | 4 =
500k | 5 = 1M
G004
Bus sharing
minimum
update in-
terval
1B, 1C, 1D
1
60
s
0
3169
550C
60
G003
Signal shar-
ing mini-
mum up-
date interval
1
60
s
0
3168
550C
5F
Signal sharing
via BUS
G012
Signal shar-
ing Pe
0
1
0
3174
550C
65
0 = O | 1 = On
G013
Signal shar-
ing Pc
1B, 1C, 1D
0
1
0
3175
550C
66
0 = O | 1 = On
G014
Signal shar-
ing S3
0
1
0
3176
550C
67
0 = O | 1 = On
BUS Settings
Modbus DI sig-
nal
X001
Bus shared
Heating
0
1
0
4043
550F
CA
0 = O | 1 = On
X002
Bus shared
Preset OD
0
1
0
4044
550F
CB
0 = O | 1 = On
X003
Bus shared
Defrost start
0
1
0
4045
550F
CC
0 = O | 1 = On
X004
Bus shared
Main switch
0
1
0
4046
550F
CD
0 = O | 1 = On
Modbus Sensor
signal
X005
Bus shared
Pc
-1
200
barg
2
4047
550F
CE
X006
Bus shared
Pe
-1
200
barg
2
4048
550F
CF
X007
Bus shared
S2
-200
200
°C
1
4049
550F
D0
X008
Bus shared
S3
-200
200
°C
1
4050
550F
D1
X009
Bus shared
S4
-200
200
°C
1
4051
550F
D2
X010
Bus shared
Ext. ref.
-100
100
1
4052
550F
D3
Alarms status
X015
Number of
active
alarms
0
100
0
4055
550F
D6
X016
Alarm noti-
cation
0
1
0
4056
550F
D7
0 = No alarms | 1 =
Alarms active
X040
Alarm status
0
1
0
4057
550F
D8
0 = O | 1 = On
X017
Warning sta-
tus
0
1
0
4058
550F
D9
0 = O | 1 = On
X018
Error status
0
1
0
4059
550F
DA
0 = O | 1 = On
Valve status
X027
Valve cur-
rent position
0
10000
steps
0
4068
550F
E3
X028
Valve target
position
0
10000
steps
0
4069
550F
E4
X031
Service
number of
steps
-32767
32767
0
4072
550F
E7
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 69
Superheat controller, Type EKE 1A, 1B, 1C, 1D

Other manuals for Danfoss EKE 1C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1C and is the answer not in the manual?

Danfoss EKE 1C Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1C
CategoryController
LanguageEnglish

Related product manuals