EasyManuals Logo
Home>Danfoss>Controller>EKE 1C

Danfoss EKE 1C User Manual

Danfoss EKE 1C
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
ID
Symptom
Possible cause/Reaction
Solution
4
Liquid hammer in compres-
sor (noisy or unusual com-
pressor sound) and /or frost
on the suction line
Superheat reference set too low.
Increase the SH reference by changing the SH min.
max. parameter.
Superheat is too low.
Make sure SH Close function is ON.
Increase the values of SH close and SH min.
Also check section "Too low superheat"
Inaccurate SH measurement or slow response in S2 sen-
sors.
Ensure that S2 sensor is secured on suction line.
Insulate temperature sensor properly.
Check the product installation guide section tempera-
ture sensor.
Refrigerant or pressure transmitter is not set correctly.
Check the related parameters.
5
Too Low superheat
Min. SH parameter is too low set.
Raise the min. SH parameter.
Valve Cannot Close fully.
Reduced the Valve OD or forced opening time at Start
up.
Valve OD too large at start up.
Use P-control.
Reduce Start OD.
Inaccurate superheat.
Mounting position of Temperature sensor. Place sensor
close to evaporator.
High-pressure drop-in suction line.
Mounting position of the pressure transmitter. Place
the transmitter close to evaporator.
Check the product installation guide section tempera-
ture sensor.
Valve is stuck at open.
Check valve installation.
Liquid returns to compressor.
Check section Liquid hammering.
6
High superheat
Lack of sub-cooling.
Limit max opening degree of the valve setting in con-
troller.
Check refrigeration system capacity and compare with
expansion valve capacity. Use proper valve size suitable
for the system.
Controller is not setup/tuned properly.
Check the controller superheat settings SH min, SH max
and sensors connected to it.
Tune PID parameters in the controller.
Wrong valve selected from the controller list or undersized
valve installed.
Check the right valve type and setting or use the ap-
propriate valve size for the needed condition.
Seasonally high load condition or overloaded the system.
Check the heat exchanger for dirt's.
Check superheat performance.
7
Too high or too low meas-
ured superheat
Wrong sensor type, refrigerant type, pressure transmitter
type and/or range.
Check the related setting and range.
In case of oset in sensor or pressure transmitter, per-
form the sensor correction.
Always use accurate pressure transmitter
8
Measured Superheat is
higher than reference -
more than 5K for 5 - 10 min.
Load condition has changed, and the superheat controller
is too slow to adapt to the change.
TN can be adjusted to 20% lower and Kp can be adjus-
ted to be 20% higher, monitor that the adjustment
doesn’t make the valve OD and Pe/Te oscillate.
Compressor capacity has changed, and the superheat con-
troller is too slow to adapt to the change.
Compensation for compressor change is done with
KpTe in this case KpTe can be adjusted to be 20% high-
er.
Missing valve capacity.
Check if valve OD is close to 100 %, if so, the valve is
missing capacity, check if sub cooling is OK.
System might have loss charge.
Measured Superheat is low-
er than reference - lower 3K
SH close parameter is disabled or not setup optimally.
Enable the SH close function and set the setpoint 2K
below the reference.
Compressor capacity has changed, and the superheat con-
troller is act too aggressive to adapt to the change.
Compensation for compressor change is done with
KpTe in this case KpTe can be adjusted to be 20% lower.
9
Fluctuating superheat
The S2 sensor not in good contact with the suction line.
Check proper mounting of the temperature sensor.
Fast change in load and ambient condition.
Wait for the stable condition and check again.
Periodic ash gas at the valve inlet.
Secure stable sub cooling
Aggressive gain Kp and Kp Te parameter.
Decrease gain in the controller, ex set SH Tn to be 20 %
higher and reduce Kp 20%, if still SH is uctuating, re-
duce KpTe by 20%.
Try with the higher SH reference.
10
Negative superheat
Wrong sensor type, refrigerant type, pressure transmitter
type and range.
Check the related setting and range.
During start up suction pressure is low because of low Am-
bient temperature.
Check the startup problem.
System is not running.
Check the system.
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 77
Superheat controller, Type EKE 1A, 1B, 1C, 1D

Other manuals for Danfoss EKE 1C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1C and is the answer not in the manual?

Danfoss EKE 1C Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1C
CategoryController
LanguageEnglish

Related product manuals