BC-HM VI.72.M4.02 Danfoss 11/97 33
Factory settings - System types 2-A and 2-B
Row ← (–) Column 0-4 (+) →
0-9
01234
0 P0.0 P0.1 P0.2 P0.3 P0.4
Status Software System Time switch Slave
generation number channel select adress
F: 2 F: 0.0 F: 15
1 P1.0 P1.1 P1.2 P1.3 P1.4
S1 actual S1 reference Total stop Balance Motor
flow flow F: 0 temperature constant
temperature temperature F: 60 °C F: 120 s
2 P2.0 P2.1 P2.4
S2 actual S2 reference X
p
- propor-
room room tional band
temperature temperature F: 70 K
3 P3.0 P3.1 P3.4
S3 actual S3 reference T
n
- integra-
temperature frost tion time
temperature F: 20 s
F: 2 °C
4 P4.0 P4.1 P4.2 P4.4
S4 actual S4 return limit Return limit N
z
-
return max./min. amplification neutral zone
temperature F: 40 °C F: -4 times F: 3 K
5 P5.0 P5.3 P5.4
S5 actual S5 scale mid- Tmax
ext. setpoint point for ext. flow
setpoint temperature
F: 50/20 °C F: 90 °C
6 P6.0 P6.2 P6.3 P6.4
S6 actual Compensation Compensation Tmin
temperature base point I factor I flow temp.
F: 5 °C F: 0 times F: 6 °C
7 P7.0 P7.1 P7.2 P7.3 P7.4
S1 actual Alarm code Compensation Compensation K
p
- propor-
flow/room base point II faxtor II tional factor
temperature F: 25 °C F: 0 times F: 5 times
8 P8.0
Normal Settings in connection with sensor S2
flow/room
temperature Settings in connection with sensors S3, S4 and S6,
F: 60 20 °C and ext. setpoint S5
9 P9.0 F: Factory setting
Reduced
flow/room
temperature
F: 40 15 °C
For further information see page 15 to 21.