EasyManua.ls Logo

Danfoss FC 100 - Page 123

Danfoss FC 100
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Surroundings:
Enclosure enclosure type D IP 00, IP 21, IP 54
Enclosure enclosure type D, E IP 21, IP 54
Enclosure kit available enclosure type D IP 21/TYPE 1/IP 4X top
Vibration test 1.0 g
Max. relative humidity 5%-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated class 3C2
Aggressive environment (IEC 721-3-3), coated class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Max. 113° F [45° C] (AVM switching mode only!) and max. 104° F [40°
C] over a 24 hour period.
Ambient temperature
Max. 104° F [40° C] (SFAVM switching mode only!) and max. 95° F [35°
C] over a 24 hour period.
Derating for high ambient temperature, see the Design Guide, section on Special Conditions
Minimum ambient temperature during full-scale operation 32° F [0° C]
Minimum ambient temperature at reduced performance 14° F [-10° C]
Temperature during storage/transport -13°-+149°/158° F [-25°-+65°/70° C]
Maximum altitude above sea level without derating 3280 ft [1000 m]
Maximum altitude above sea level with derating 9842 ft [3000 m]
Derating for high altitude, see section on special conditions.
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN
61000-4-6
See section on special conditions.
Control card performance:
Scan interval : 5 ms
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other
high-voltage terminals.
The USB connection is
not galvanically isolated from protection ground. Use only
isolated laptop/PC as connection to the USB connector on VLT HVAC Drive or an
isolated USB cable/drive.
VLT
®
HVAC DRIVE High Power
Instruction Manual
5. General Specifications
MG.11.F1.22 - VLT
®
is a registered Danfoss trademark.
123
5

Table of Contents

Related product manuals