4.2. Quick Set-up
4.2.1. Quick Menu Mode
Parameter Data
The graphical display (GLCP) provides access
to all parameters listed under the quick me-
nus. The numeric display (NLCP) only provides
access to the Quick Set-up parameters. To set
parameters using the [Quick Menu] button,
enter or change parameter data or settings in
accordance with the following procedure:
1. Press the Quick Menu button
2.
Use the [] and [] buttons to find
the parameter you want to change.
3. Press [OK].
4.
Use [] and [] buttons to select the
correct parameter setting.
5. Press [OK].
6. To move to a different digit within a
parameter setting, use the [] and
[] buttons.
7. Highlighted area indicates digit se-
lected for change.
8. Press [Cancel] button to disregard
change, or press [OK] to accept
change and enter the new setting.
Example of Changing Parameter Data
Assume parameter
22-60, Broken Belt Func-
tion
is set to [Off]. However, you should still
monitor the fan belt condition - non-broken or
broken - according to the following procedure:
1. Press the Quick Menu key.
2. Choose Function Set-ups with the
[] button.
3. Press [OK].
4. Choose Application Settings with the
[] button.
5. Press [OK].
6. Press [OK] again for fan functions.
7. Choose the broken belt function by
pressing [OK].
8. With [] button, choose [2] Trip.
The adjustable frequency drive will now trip if
a broken fan belt is detected.
Select [My Personal Menu] to display only the parameters that have been pre-selected and pro-
grammed as personal parameters. For example, an AHU or pump OEM may have pre-programmed
these to be in My Personal Menu during factory commissioning to make on-site commissioning/
fine tuning simpler. These parameters are selected in
par. 0-25 Personal Menu
. Up to 20 different
parameters can be programmed in this menu.
If [No Operation] is selected in
par. Terminal 27 Digital Input
, no connection to +24 V on terminal
27 is necessary to enable start.
If [Coast Inverse] (factory default value) is selected in
par. Terminal 27 Digital Input
, a connection
to +24 V is necessary to enable start.
Select [Changes Made] to get information about:
The last 10 changes. Use the up/down navigation keys to scroll between the last 10
changed parameters.
The changes made since default setting.
Select [Loggings] to get information about the display line readouts. The information is shown in
graphs.
VLT
®
HVAC DRIVE High Power
Instruction Manual