3.7.3. Speed Up/Slow
Terminals 29/32 = Speed up/Slow: .
Terminal 18 = Par. 5-10 [9]
Start
(default)
Terminal 27 = Par. 5-12 [19]
Freeze
reference
Terminal 29 = Par. 5-13 [21]
Speed
up
Terminal 32 = Par. 5-14 [22]
Slow
Note: Terminal 29 only in FC x02 (x=series
type).
3.7.4. Potentiometer Reference
Voltage reference via a potentiometer:
Reference Source 1 = [1]
Analog in-
put 53
(default)
Terminal 53, Low Voltage = 0 Volt
Terminal 53, High Voltage = 10 Volt
Terminal 53, Low Ref./Feedback = 0
RPM
Terminal 53, High Ref./Feedback =
1500 RPM
Switch S201 = OFF (U)