5. General Specifications
Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P110
110
P132
132
P160
160
P200
200
P250
250
P315
315
P355
355
P400
400
P450
450
Typical Shaft Output [HP] at 460V 150 200 250 300 350 450 500 550 600
IP 00   D3 D3 D4 D4 D4 E2 E2 E2 E2
IP 21   D1 D1
D2 D2 D2 E1 E1 E1 E1
IP 54   D1 D1 D2 D2 D2 E1 E1 E1 E1
Output current
Continuous (3 x 400 V) [A] 212 260 315 395 480 600 658 745 800
Intermittent (3 x 400 V) [A] 233 286 347 435 528 660 724 820 880
Continuous (3 x 460-500 V) [A] 190 240 302 361 443 540 590 678 730
Intermittent (3 x 460-500 V) [A]
209 264 332 397 487 594 649 746 803
Continuous kVA (400 V AC) [kVA] 147 180 218 274 333 416 456 516 554
Continuous kVA (460 V AC) [kVA]
151 191 241 288 353 430 470 540 582
Max. cable size:
(line power, motor, brake) [mm
2
/ AWG] 
2)
2x70
2x2/0
2x185
2x350 mcm
4x240
4x500 mcm
Max. input current
 
Continuous (3 x 400 V) [A] 204 251 304 381 463 590 647 733 787
Continuous (3 x 460/500V) [A] 183 231 291 348 427 531 580 667 718
Max. pre-fuses
1)
[A]
300 350 400 500 600 700 900 900 900
Environment
Estimated power loss
at rated max. load [W] 
4)
3234 3782 4213 5119 5893 7630 7701 8879 9428
Weight enclosure IP 00 [kg] 81.9 90.5 111.8 122.9 137.7 221.4 234.1 236.4 277.3
Weight enclosure IP 21 [kg] 95.5 104.1
125.4 136.3 151.3 263.2 270.0 272.3 313.2
Weight enclosure IP 54 [kg] 95.5 104.1 125.4 136.3 151.3 263.2 270.0 272.3 313.2
Efficiency 
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
1)
 For type of fuse, see section 
Fuses.
2)
 American Wire Gauge
3)
 Measured using 16.4 ft. [5 m] shielded motor cables at rated load and rated frequency.
4)
 The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the adjustable frequency drive and vice versa.
If the switching frequency is raised from nominal, the power losses may rise significantly.
LCP and typical control card power consumption values are included. Further options and customer load may add up to 30 W to the losses. (though typically only 4W extra for a fully loaded
control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).
VLT
®
 HVAC DRIVE High Power
Instruction Manual
5. General Specifications
 MG.11.F1.22 - VLT
®
 is a registered Danfoss trademark.   
117
5