Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P110
110
P132
132
P160
160
P200
200
P250
250
P315
315
P355
355
P400
400
P500
500
P560
560
Typical Shaft Output [HP] at 575 V 150 200 250 300 350 400 450 500 600 650
IP 00 D3 D3 D4 D4 D4 D4 E2 E2 E2 E2
IP 21 D1 D1
D2 D2 D2 D2 E1 E1 E1 E1
IP 54 D1 D1 D2 D2 D2 D2 E1 E1 E1 E1
Output current
Continuous (3 x 550 V) [A] 162 201 253 303 360 418 470 523 596 630
Intermittent (3 x 550 V) [A] 178 221 278 333 396 460 517 575 656 693
Continuous (3 x 575-690V) [A] 155 192 242 290 344 400 450 500 570 630
Intermittent (3 x 575-690 V) [A]
171 211 266 319 378 440 495 550 627 693
Continuous kVA (550 V AC) [kVA] 154 191 241 289 343 398 448 498 568 600
Continuous kVA (575 V AC) [kVA]
154 191 241 289 343 398 448 498 568 627
Continuous kVA (690 V AC) [kVA] 185 229 289 347 411 478 538 598 681 753
Max. cable size:
(line power, motor, brake) [mm
2
/ AWG]
2)
2x70
2x2/0
2x185
2x350 mcm
4x240
4x500 mcm
Max. input current
Continuous (3 x 550 V) [A] 158 198 245 299 355 408 453 504 574 607
Continuous (3 x 575 V) [A] 151 189 234 286 339 390 434 482 549 607
Continuous (3 x 690 V) [A] 155 197 240 296 352 400 434 482 549 607
Max. pre-fuses
1)
[A]
225 250 350 400 500 600 700 700 900 900
Environment
Estimated power loss
at rated max. load [W]
4)
3114 3612 4293 5156 5821 6149 6449 7249 8727 9673
Weight enclosure IP 00 [kg] 81.9 90.5 111.8 122.9 137.7 151.3 221 221 236 277
Weight enclosure IP 21 [kg] 95.5 104.1
125.4 136.3 151.3 164.9 263 263 272 313
Weight enclosure IP 54 [kg] 95.5 104.1 125.4 136.3 151.3 164.9 263 263 272 313
Efficiency
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
1)
For type of fuse, see section
Fuses.
2)
American Wire Gauge
3)
Measured using 16.4 ft. [5 m] shielded motor cables at rated load and rated frequency.
4)
The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the adjustable frequency drive and vice versa.
If the switching frequency is raised from nominal, the power losses may rise significantly.
LCP and typical control card power consumption values are included. Further options and customer load may add up to 30 W to the losses. (though typically only 4W extra for a fully loaded control card, or
options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).
5. General Specifications
VLT
®
HVAC DRIVE High Power
Instruction Manual
118
MG.11.F1.22 - VLT
®