Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possible to store
up to 120 samples in the memory for later reference.
Efficient Parameter Set-up for HVAC Ap-
plications
The parameters can easily be set up for the vast majority of the HVAC applications only by using
the [Quick Set-up] option.
After pressing [Quick Menu], the different areas in the quick menu are listed. See also illustration
6.1 below and tables Q3-1 to Q3-4 in the following 
Function Set-ups
 section.
Example of using the Quick Set-up op-
tion
Assume you want to set the ramp-down time
to 100 seconds!
1. Press [Quick Set-up]. The first 
par.
0-01 Language
 in Quick Set-up ap-
pears.
2. Press [▼] repeatetly until 
par. 3-42
Ramp 1 Ramp-down Time
 appears
with the default setting of 20 sec-
onds.
3. Press [OK].
4. Use the [◀] button to highlight the
3rd digit before the comma.
5. Change '0' to '1' by using the [▲] but-
ton.
6.
Use the [▶] button to highlight the
digit '2'.
7.
Change '2' to '0' with the [▼] button.
8. Press [OK].
The new ramp-down time is now set to 100
seconds.
It is recommended to do the set-up in the or-
der listed.
NOTE
A complete description of the
function is found in the param-
eter sections of this Instruction
Manual.
 4.1: Quick Menu view.
The QUICK Set-up menu gives access to the
12 most important set-up parameters of the
drive. After programming, the drive will, in
most cases, be ready for operation. The 12
(see footnote) quick menu parameters are
shown in the table below. A complete descrip-
tion of the function is given in the parameter
sections of this manual.