EasyManuals Logo

Danfoss FC 300 Series User Manual

Danfoss FC 300 Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
NOTE!
Protection mode and trip delay features (14-25 Trip Delay at
Torque Limit and 14-26 Trip Delay at Inverter Fault) may delay
the activation of the mechanical brake in an alarm condition.
These features must be disabled in hoisting applications.
2-20 Release Brake Current
Range: Function:
Application
dependent
*
[Application
dependant]
Set the motor current for release of
the mechanical brake, when a start
condition is present. The default
value is the maximum current the
inverter can provide for the
particular power size. The upper
limit is specified in 16-37 Inv. Max.
Current.
NOTE!
When Mechanical brake control
output is selected but no
mechanical brake is connected,
the function will not work by
default setting due to too low
motor current.
2-21 Activate Brake Speed [RPM]
Range: Function:
Application
dependent
*
[0 - 30000
RPM]
Set the motor speed for activation
of the mechanical brake when a
stop condition is present. The
upper speed limit is specified in
4-53 Warning Speed High.
2-22 Activate Brake Speed [Hz]
Range: Function:
Application
dependent
*
[Application
dependant]
Set the motor frequency for
activation of the mechanical
brake when a stop
condition is present.
Parameter Descriptions FC 300 Programming Guide
3-30 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
CategoryDC Drives
EnclosureIP20
Communication OptionsCANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Input Voltage380-500V AC

Related product manuals