EasyManuals Logo
Home>Danfoss>DC Drives>FC 300 Series

Danfoss FC 300 Series User Manual

Danfoss FC 300 Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
3-17 Reference Resource 3
Option: Function:
Select the reference input to be used
for the third reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up to
three different reference signals. The
sum of these reference signals
defines the actual reference.
[0] No function
[1] Analog input 53
[2] Analog input 54
[7] Frequency input 29
[8] Frequency input 33
[11]
*
Local bus reference
[20] Digital pot.meter
[21] Analog input X30-11
[22] Analog input X30-12
[29] Analog Input X48/2
3-18 Relative Scaling Reference Resource
Option: Function:
Select a variable value to be added to the
fixed value (defined in 3-14 Preset Relative
Reference). The sum of the fixed and variable
values (labeled Y in the figure below) is
multiplied by the actual reference (labeled X
in the figure below). The result is then added
to the actual reference (X+X*Y/100) to give
the resulting actual reference.
This parameter cannot be adjusted while the
motor is running.
[0]
*
No function
[1] Analog input
53
[2] Analog input
54
[7] Frequency
input 29
[8] Frequency
input 33
[11] Local bus
reference
[20] Digital
pot.meter
3-18 Relative Scaling Reference Resource
Option: Function:
[21] Analog input
X30-11
[22] Analog input
X30-12
[29] Analog Input
X48/2
3-19 Jog Speed [RPM]
Range: Function:
Application
dependent
*
[Application
dependant]
Enter a value for the jog speed
n
JOG
, which is a fixed output
speed. The adjustable frequency
drive runs at this speed when the
jog function is activated. The
maximum limit is defined in
4-13 Motor Speed High Limit
[RPM].
See also 3-80 Jog Ramp Time.
3.5.3 Ramps
3-4* Ramp 1
For each of four ramps (par. group 3-4*, 3-5*, 3-6* and 3-7*),
configure the ramp parameters: ramp type, ramping times
(duration of acceleration and deceleration) and level of jerk
compensation for S ramps.
Start by setting the linear ramping times corresponding to
the figures.
If S-ramps are selected, then set the level of non-linear jerk
compensation required. Set jerk compensation by defining
the proportion of ramp-up and ramp-down times where
acceleration and deceleration are variable (i.e., increasing or
decreasing). The S-ramp acceleration and deceleration
settings are defined as a percentage of the actual ramp time.
Parameter Descriptions FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark 3-35
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals