FC 300 Instruction Manual
How to Program
" 5-** Digital In/Out
Par.
No. #
Parameter d escription Default value 4-set-up Change
during
operation
Conver-
sion index
Type
5-0* Digital IO mode
5-00 Digital I/O mode [0] PNP All set-ups FALSE - Uint8
5-01 Te rminal 27 m o de [0] Input All set-ups FALSE - Uint8
5-02 Te rminal 29 m o de [0] Input All set-ups FALSE - Uint8
5-1* Digital inputs
5-10 Terminal 18 digital input [8] Start All set-ups TRUE - Uint8
5-11 Terminal 19 digital input [10] Reverse All set-ups TRUE - Uint8
5-12 Terminal 27 digital input [2] Coast inverse All set-ups TRUE - Uint8
5-13 Terminal 29 digital input [14] Jog All set-ups TRUE - Uint8
5-14 Terminal 32 digital input [24] Set-up select bit 1 All set-ups TRUE - Uint8
5-15 Terminal 33 digital input [23] Set-up select bit 0 All set-ups TRUE - Uint8
5-3* Digital outputs
5-30 Terminal 27 digital output [0] No operation All set-ups TRUE - Uint8
5-31 Terminal 29 digital output [0] No operation All set-ups TRUE - Uint8
5-4* Relays
5-40 Function relay [0] No operation All set-ups TRUE - Uint8
5-41 On delay, relay 0.01 s All set-ups TRUE -2 Uint16
5-42 Off delay, relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse input
5-50 Term. 29 low frequency 100 Hz All set-ups TRUE 0 Uint32
5-51 Term. 29 high frequency 100 Hz All set-ups TRUE 0 Uint32
5-52 Te rm. 29 low ref./fee db. value 0.000 Unit All set-ups TRUE -3 Int32
5-53 Te rm. 29 high ref./feedb. value 1500.000 Unit All set-ups TRUE -3 Int32
5-54 Pulse filter time constant #29 100 ms All set-ups FALSE -3 U int16
5-55 Term. 33 low frequency 100 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 high frequency 100 Hz All set-ups TRUE 0 Uint32
5-57 Te rm. 33 low ref./fee db. value 0.000 Unit All set-ups TRUE -3 Int32
5-58 Te rm. 33 high ref./feedb. value 1500.000 Unit All set-ups TRUE -3 Int32
5-59 Pulse filter time constant #33 100 ms All set-ups FALSE -3 U int16
5-6* Pulse outpu t
5-60 Terminal 27 pulse output variable [0] No operation All set-ups FALSE - Uint8
5-62 Pulse output maximum frequency #27 5000 Hz All set-ups FALSE 0 Uint32
5-63 Terminal 29 pulse output variable [0] No operation All set-ups FALSE - Uint8
5-65 Pulse output maximum frequency #29 5000 Hz All set-ups FALSE 0 Uint32
5-7* 24V encoder input
5-70 Term 32/33 encoder resolution 1024 All set-ups FALSE 0 Uint16
5-71 Term 32/33 encoder direction [0] Clockwise All set-ups FA LSE - Uint8
*