FC 300 Instruction Manual
How to Program
" 4-** Limits / Warnings
Par.
No. #
Parameter d escription Default value 4-set-up Change
during
operation
Conver-
sion index
Type
4-1* Motor limits
4-10 Motor speed direction [2] Both directions All set-ups FALSE - Uint8
4-11 Motor speed low limit [RPM] 0 RPM All set-ups TRUE 67 U int16
4-13 Motor speed high limit [RPM] 3600 RPM All set-ups TRUE 67 Uint16
4-16 Torque limit motor mode 160.0 % All set-ups TRUE -1 Uint16
4-17 Torque limit generator mode 160.0 % All set-ups TRUE -1 Uint16
4-18 Current limit 160.0 % All set-ups TRUE -1 Uint16
4-19 Max output frequency 132.0 Hz All set-ups FALSE -1 U int16
4-5* Adj. warnings
4-50 Warning current low 0.00 A All set-ups TRUE -2 Uint16
4-51 Warning current high Par. 16-37 All set-ups TRUE -2 Uint16
4-52 Warning speed low 0 RPM All set-ups TRUE 67 Uint16
4-53 Warning speed high Par. 4-13 All set-ups TRUE 67 Uint16
4-58 Missing motor phase function [0] Off All set-ups FALSE - Uint8
4-6* Speed bypass
4-60 Bypass speed from [RPM] 0 RPM All set-ups TRUE 67 Uint16
4-62 Bypass speed to [RPM] 0 RPM All set-ups TRUE 67 Uint16
*
default setting ()display text []value for use in communication via serial communication port
50
MG.33.A
4.22 - VLT is a registered Danfoss trademark