EasyManua.ls Logo

Danfoss FC 302 - Speed Up;Slow down; Potentiometer Reference

Danfoss FC 302
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FC 300 Instruction Manual
How to Program
" Speed up/slow down
Terminals 29/32 = Speed up/slow down.
Par. 5 Digital input = Pulse start -10
Par. 5 Digital input = Freeze reference -12
Par. 5 Digita l input = Speed up -13
Par. 5-14 Digital input = Slow down
" Potentiometer Reference
Voltage reference via a potentiometer.
Par. 3-15 Reference Resource 1 [1]
= Analog Input 53
Par. 6-10 Terminal 53, Low Voltage =0Volt
Par. 6-11 Terminal 53, High Voltage =10Volt
Par. 6-14 Terminal 53, Low Ref./Feedb.
Value Value =0RPM
Par. 6-15 Terminal 53, High Ref./Feedb.
Value Value =1,500RPM
Switch S201 = OFF (U)