Externals:
- Enclosure ............................................................................................................................. IP 55 (IP56, IP66)
- Vibration test ........................................................................................................ (IEC 68 see page 18-3) 1 g
- Max. relative humidity ................................................... 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
- Ambient temperature .......................................................................Max. 40°C (24-hour average max. 35°C)
Derating for high ambient temperature, see chapter 18.
- Min. ambient temperature in full operation .................................................................................................0°C
- Min. ambient temperature at reduced performance.............................................................................. -10°C
- Temperature during storage/transport..................................................................................... -25 - +65/70°C
- Max. altitude above sea level ................................................................................................3,300 ft./1000 m
Derating for air pressure, see chapter 18.
- EMC standards applied, Emission...................................EN 50081-1/2, EN 61800-3, EN 55011, EN 55014
Immunity ................... EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4
EN 61000-4-5, ENV 50140, ENV 50141
- Safety standards applied, ............................................................................ EN 60146, EN 50178, EN 60204
UL508
Protection:
Thermal overload protection of motor and electronics.
Monitoring of the intermediate circuit voltage ensures that the inverter cuts out if the intermediate circuit
voltage gets too high or too low.
If an AC line phase is missing, the inverter will cut out when a load is placed on the motor.
Overcurrent, and voltage transients protection.
2-4
MG.03.B6.22 - VLT is a registered Danfoss trademark
General Technical Data