13
Installation Instructions
GB
Option 74 - Date format for calendar clock
This allows date format to be chosen. Press +
until Option 74 is displayed, use V and Λ to select
required setting.
Setting 0 European format (dd/mm/yy), (Factory setting)
Setting 1 North American format (mm/dd/yy)
Option 81 - Thermostat calibration bias
This allows the thermostat calibration to be biased
by up to ±1.5°C. Press + until Option 81 is displayed,
use V and Λ to select required setting.
Setting Any value between ±1.5 in 0.5°C steps (Factory setting is 0°C)
Option 90 - De ne remote sensor type, A models only
This allows type of remote sensor input type to be
de ned. Press + until Option 90 is displayed, use V
and Λ to select required setting.
Setting 0 No remote sensor  tted (Factory setting)
Setting 1 Remote room or duct sensor  tted, internal sensor disabled,
Setting 2 Remote limit sensor  tted, refer to option 93 to de ne set-
point
Setting 3 Con gured as digital input for window, card reader or
teleswitch, refer to option 94 to de ne o/c or s/c.
Option 93 - Set limit sensor set-point, A models only,
(option 90 set to 2)
This allows the thermostat limit sensor to be set,
typical application is  oor heating. Press + until
Option 93 is displayed, use V and Λ to select
required setting. If the temperature sensed by
the limit sensor exceeds the limit setting the
output will be turned o until the temperature
has dropped by 2°C. “F10” will  ash in the display
while the output is disabled.
Setting Any value between 20 - 50°C (Factory setting is 27°C)