27
Option 10 - Frost/ thermostat mode setting
This feature allows the default frost/thermostat 
mode temperature to be set. Press + until Option 10 
is displayed, use Λ and V to select required setting.
5-40°C - Factory setting is 5°C, but can be changed to any value 
between 5-40°C.
User Instructions
GB
Option 11  - Start-up method
Your thermostat can start up the system in three 
di erent ways. Press + until Option 11 is displayed, 
use Λ and V to select required setting.
Setting 0 Normal: Heating is turned up or down at the programmed 
times.
Setting 1 Optimum start control (OSC) (or Comfort Setting): This 
allows you to programme the time at which you would like 
to be up to the required temperature. The thermostat then 
calculates how soon before the required time the heating 
is turned up. This will vary with weather conditions ranging 
from a maximum of 120 minutes to 0 minutes before 
the programmed event time. This setting must be used 
together with option 12 to match the optimiser setting to 
the building in which it is installed.
Setting 2 Delay start (or Economy Setting): This is an alternative to 
OSC. Set the event times in the normal way taking into 
account the time that the building takes to heat on an 
average day. The thermostat monitors switch on time, 
actual temperature and wanted temperature and delays 
the start of the heating if the actual temperature is close to 
the programmed temperature.