TP9000
10
GB
PL
GR
ES
GB
c) Use + and - keys to scroll backwards and forwards between
options then
V and Λ keys to change the option settings. The
fl ashing digit on the right hand of the display indicates the
number of the selected option. The large characters display the
option value selected.
d) To return to RUN, press and hold PROG until the display returns
to RUN mde.
Option 30 - Set upper limit of temperature range
This allows the upper limit of the thermostat
setting range to be electronically limited. Press +
until Option 30 is displayed, use V and Λ to select
required setting.
Setting 40 - 5°C (factory setting is 30°C)
Option 31 - Set lower limit of temperature range
This allows the lower limit of the thermostat
setting range to be electronically limited. Press +
until Option 31 is displayed, use V and Λ to select
required setting.
Setting 5 - 40°C (factory setting is 5°C)
Option 32 - Enable Off at lower limit
This enables an OFF function to be selected if a
set point below the lower limit is selected. Press +
until Option 32 is displayed, use
V and Λ to select
required setting.
Setting 0 Disabled
Setting 1 Enabled (factory setting)
Option 33 - Enable On at upper limit
This enables an ON function to be selected if a set
point above the upper limit is selected. Press +
until Option 33 is displayed, use
V and Λ to select
required setting.
Setting 0 Disabled (factory setting)
Setting 1 Enabled