Danfoss Heating
11
GB
PL
GR
ES
GB
Option 34 - Select On/Off or Chrono-proportional
This allows the thermostat to be set to run in On/Off
mode or for a chrono-proportional cycle rate to be
selected. Press + until Option 34 is displayed, use V
and Λ to select required setting.
0 On/Off
3 3 cycles per hour
6 6 cycles per hour (factory setting)
9 9 cycles per hour
12 12 cycles per hour
Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12)
(seek advice prior to adjusting)
This adjusts the integration time of the PI
algorithm to increase control accuracy. It is only
active if option 34 has been set to Chrono 3, 6,
9 or 12. It should only be adjusted after seeking
advice from the manufacturer. Press + until
Option 35 is displayed, use
V and Λ to select
required setting.
2.5 Integration time set to 2.5% (factory setting)
5 Integration time set to 5%
10 Integration time set to 10%
Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press + until Option 36 is
displayed, use
V and Λ to select required setting.
Setting 0 No limit (factory setting)
Setting 1 Limited to ±2°C
Setting 2 No override allowed