Generic EMC standards/product standards
Standard / environment Residential, commercial and light in-
dustry
Industrial environment
Cable-borne Radiated Cable-
borne
Radiated
EN 61000-6-3 Class B Class B
EN 61000-6-4 Class A Class A
EN 61800-3
UNRESTRICTED
Class B
Class A
Class B
Class A
Group 2
Class A
Group 2
Class A
EN 61800-3 RESTRICTED Class A Class A Group 2
Class A
Group 2
Class A
EMC emission
The following system results are achieved on a system
consisting of a VLT Series 2800 with screened/arm-
oured control cable, control box with potentiometer,
screened/armoured motor cable and screened/arm-
oured brake cable as well as an LCP2 with cable.
VLT 2803-2875 Emission
Industrial environment Residential, commercial and light industry
EN 55011 class 1A EN 55011 class 1B
Setup
Cable-borne
150 kHz- 30 MHz
Radiated
30 MHz - 1 GHz
Cable-borne
150 kHz - 30 MHz
Radiated
30 MHz - 1 GHz
3 x 480 V version with 1A
RFI filter
Yes
25 m screened/arm-
oured
Yes
25 m screened/arm-
oured
No No
3 x 480 V version with 1A
RFI filter (R5: For IT
mains)
Yes
5 m screened/arm-
oured
Yes
5 m screened/arm-
oured
No No
1 x 200 V version with 1A
RFI filter
1.
Yes
40 m screened/arm-
oured
Yes
40 m screened/arm-
oured
Yes
15 m screened/arm-
oured
No
3 x 200 V version with 1A
RFI filter (R4: For use
with RCD)
Yes
20 m screened/arm-
oured
Yes
20 m screened/arm-
oured
Yes
7 m screened/arm-
oured
No
3 x 480 V version with 1A
+1B RFI filter
Yes
50 m screened/arm-
oured
Yes
50 m screened/arm-
oured
Yes
25 m screened/arm-
oured
No
1 x 200 V version with 1A
+1B RFI filter
1.
Yes
100 m screened/
armoured
Yes
100 m screened/arm-
oured
Yes
40 m screened/arm-
oured
No
VLT 2880-2882 Emission
Industrial environment Residential, commerce and light industry
EN 55011 class 1A EN 55011 class 1B
Setup
Cable-borne
150 kHz- 30 MHz
Radiated
30 MHz - 1 GHz
Cable-borne
150 kHz - 30 MHz
Radiated
30 MHz - 1 GHz
3 x 480 V version with 1B
RFI filter
Yes
50 m
Yes
50 m
Yes
50 m
No
1. For VLT 2822-2840 3 x 200-240 V the same values apply as for the 480 V version with 1A RFI filter.
EN 55011: EmissionLimits and methods of measurement of radio disturbance characteristics of indus-
trial, scientific and medical (ISM) high-frequency equipment.
Class 1A:
Equipment used in an industrial environment.
Class 1B:
Equipment used in areas with a public supply network (residential, commerce and light industry).
MG.27.E2.02 - VLT is a registered Danfoss trademark 139
All about VLT 2800

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals