Technical functions
600-605 Operating Data
Value:
Par. no. Description Display text Unit Range
600 Operating hours (OPERATING HOURS) Hours 0-130,000.0
601 Hours run (RUNNING HOURS) Hours 0-130,000.0
602 kWh counter (KWH COUNTER) kWh Depends on unit
603 Number of power-up's (POWER UP'S) Number of times 0-9999
604 Number of overtemperatures (OVER TEMP'S) Number of times 0-9999
605 Number of overvoltages (OVER VOLT'S) Number of times 0-9999
Function:
These parameters can be read out via the serial com-
munication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the frequency converter
has been operating. The value is saved every hour and
when there is a mains failure. This value cannot be
reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been oper-
ating since the reset in parameter 619 Reset of hours-
run counter. The value is saved every hour and when
there is a mains failure.
Parameter 602, kWh counter:
Gives the frequency converter's output energy in kWh.
The calculation is based on the mean kW value over
one hour. This value can be reset using parameter 618
Reset of kWh counter.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the frequency converter.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults that have
been registered on the frequency converter's heat
sink.
Parameter 605, Number of overvoltages:
Gives the number of overvoltages of the intermediate
circuit voltage in the frequency converter. This is only
counted when Alarm 7 Overvoltage is active.
NB!
Parameters 615-617 Fault log cannot be
read out via the integral control unit.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for a
trip (cut-out of the frequency converter) occurring. 10
[1-10] log values are defined.
The lowest log number [1] contains the latest/most re-
cently saved data value. The highest log number [10]
contains the oldest data value saved. If a trip occurs,
it is possible to see the cause, time and a possible val-
ue of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a
table. See the table in Warnings/alarm messages.
616 Fault log: Time
(F.LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number
of operating hours in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest log num-
ber [1] contains the latest/most recently saved data
value, and the highest log number [10] contains the
oldest data value.
Description of choice:
Read out as one value.
= factory setting, () = display text, [] = value for use in communication via serial communication port
130 MG.27.E2.02 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals