EasyManuals Logo
Home>Danfoss>DC Drives>VLT 2800

Danfoss VLT 2800 User Manual

Danfoss VLT 2800
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
i.e. it is possible to turn off the control word if you do
not wish to use it in connection with updating or reading
parameters.
Bit 11, Relay 01:
Bit 11 = “0” Relay not activated.
Bit 11 = “1” Relay 01 activated, provided Control word
bit has been chosen in parameter 323.
Bit 12, Digital output, terminal 46:
Bit 12 = “0” Digital output has not been activated.
Bit 12 = “1” Digital output has been activated, provided
Control word bit has been chosen in parameter 341.
Bit 13/14, Selection of Setup:
Bits 13 and 14 are used to choose from the four menu
Setups according to the following table:
Setup
Bit 14 Bit 13
1 0 0
2 0 1
3 1 0
411
The function is only possible when Multi-Setups is se-
lected in parameter 004 Active Setup .
Note: I parameter 507 Selection of Setup a selection is
made to define how Bit 13/14 gates with the corre-
sponding function on the digital inputs.
Bit 15 Reversing:
Bit 15 = '0' causes no reversing.
Bit 15 = '1' causes reversing.
Note: In the factory setting reversing is set to digital in
parameter 506 Reversing. Bit 15 only causes reversing
when either Ser. communication , Logic or or Logic
and is selected.
Status Word according to FC Profile
The status word is used to inform the master (e.g. a
PC) of the slave's (frequency converter) mode.
Slave•Master.
Bit Bit = 0 Bit =1
00 Control ready
01 Drive ready
02 Coasting stop
03 No trip Trip
04 Not used
05 Not used
06 Trip lock
07 No warning Warning
08 Speed • ref. Speed = ref.
09 Local control Ser. communi.
10 Outside
frequency range
Frequency limit
OK
11 Motor running
12
13 Voltage warn.
14 Current limit
15 Thermal warn.
Bit 00, Control ready:
Bit 00 = '1'. The frequency converter is ready for op-
eration.
Bit 00 = '0'. The frequency converter is not ready for
operation.
Bit 01, Drive ready:
Bit 01 = '1'. The frequency converter is ready for op-
eration, but there is an active coasting command via
the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = '0'. The frequency converter has released the
motor.
Bit 02 = '1'. The frequency converter can start the mo-
tor when a start command is given.
Bit 03, No trip/trip:
Bit 03 = '0' means that the frequency converter is not
in fault mode.
Bit 03 = '1' means that the frequency converter is trip-
ped, and that it needs a reset signal for operation to be
reestablished.
Bit 04, Not used:
Bit 04 is not used in the status word.
Bit 05, Not used:
Bit 05 is not used in the status word.
MG.27.E2.02 - VLT is a registered Danfoss trademark 117
Programming

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals