EasyManuals Logo

Danfoss VLT 5000 User Manual

Danfoss VLT 5000
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Synchronizing controller
12 MG.10.N4.02 - VLT is a registered Danfoss trademark
Technical Data
Terminals:
Type..............................................................................................................Plugs with screw connections
Maximum cable size......................................................................................................1.3 mm
2
(AWG 16)
Digital inputs, MK3A:
Terminal designations .......................................................................................................................I1 – I8
Voltage level ............................................................................................0 – 24 V DC (PNP positive logic)
Voltage threshold logical “0”............................................................................................................ 5 V DC
Voltage threshold logical “1”.......................................................................................................... 10 V DC
Maximum voltage ..........................................................................................................................28 V DC
Input impedance..................................................................................................................................4 k
Min. pulse duration (ON INT)...........................................................................................................1 msec
Galvanic isolation: All digital inputs are galvanically isolated by means of optocouplers,
but with the same common as the digital outputs.
Digital outputs, MK3C:
Terminal designations ...................................................................................................................O1 – O8
Voltage level ............................................................................................................................ 0 – 24 V DC
Maximum load ........................................................................................0.7A (with external power supply)
Update rate......................................................................................................................................1 msec
Galvanic isolation: All digital outputs are galvanically isolated by means of optocouplers,
but with the same common as the digital inputs.
External 24 V DC supply:
(see VLT 5000 manual)
Encoder input 1, MK3B (master):
Terminal designations .......................................................................................... A1, A1, B1, B1, Z1, Z1.
Incremental:
Signal level ...........................................................................................................................5 V differential
Signal type.....................................................................................................................Linedriver, RS 422
Input impedance.............................................................................................120 (Dip switch 1.3 = ON)
...................................................................................................................> 24 k (Dip switch 1.3 = OFF)
Maximum frequency......................................................................................220 kHz (at 50 % duty cycle)
Phase displacement between A and B..........................................................................................90° ±30°
Absolute:
Signal level ...........................................................................................................................5 V differential
Signal type.............................................................................................................................................SSI
Data coding ................................................................................................................................Gray code
Data length .........................................................................................................................................25 bit
Parity....................................................................................................................................................none
Clock frequency.................................................................................................................. 105 or 260 kHz
Protocol ...............................................................................................................................................Gray
Maximum positions per revolution.......................................................................................................8192
Maximum number of revolutions .........................................................................................................4096

Table of Contents

Other manuals for Danfoss VLT 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 and is the answer not in the manual?

Danfoss VLT 5000 Specifications

General IconGeneral
Frequency50/60 Hz
Output Voltage Range0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesRS-485
Ambient Temperature Range-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Input Voltage200-240V AC, 380-480V AC, 525-600V AC

Related product manuals