Point Mapping Table
The VLT 6000 parameters, along with the internal
variables and readouts for controlling the drive via
the FLN serial bus, are organized as a Point Map.
Not all parameters and readouts are supported by
the FLN protocol. FLN points 01, 02, 20, 29 and 99
are predefined. Available points and a description of
their characteristics are listed in Table 8. Parameters
which can be written to (W in the Read/Write
column) are programmable through the FLN device,
others (R) are read-only, or read and write (R/W).
TT
TT
T
able 8able 8
able 8able 8
able 8 Point Mapping
Point
Number
Descriptor
Factory
Default
(SI Units)
SI Units Slope
(SI Units)
Intercept
(SI Units)
Range On Text
Off Text
Read/
Write
Param.
number
Network
Port
Type
Note 1
01 CTLR ADDRESS 1 -- 1 0 255 -- -- R 501 Pre-
defined
02 APPLICATION 2709 -- 1 0 255 -- -- R -- Pre-
defined
Readout Points
{03} FREQ OUTPUT 0 HZ 0.1 0 16383 -- -- R 512 LAI
{06} CURRENT 0 A 0.1 0 16383 -- -- R 514 LAI
{08} POWER 0 KW 1 0 511 -- -- R 515 LAI
{10} KWH 0 KWH 3.1 0 32767 -- -- R 602 LAI
{12} RUN TIME 0 HRS 4.0 0 32767 -- -- R 601 LAI
{13} DC BUS VOLT 0 VOLTS 1 0 1023 -- -- R 518 LAI
{14} OUTPUT VOLT 0 VOLTS 1 0 1023 -- -- R 517 LAI
{15} MOTOR THERM 0 PCT 1 0 255 -- -- R 519 LAI
{16} DRIVE THERM 0 PCT 1 0 255 -- -- R 520 LAI
{17} CURR. SETU 0 -- 1 0 255 -- -- R -- LAI
{18} TIMERS STAT 0 -- -- -- -- LIMIT OK R 527-15 LDI
{19} CURRENT STAT 0 -- -- -- -- LIMIT OK R 527-14 LDI
20 OVRD TIME 1 HRS 1 0 255 -- -- W -- Pre-
defined
Status and Command Points
{21} FWD.REV FWD -- -- -- -- REV FWD R 532-8 LDI
{22} CMD FWD.REV FWD -- -- -- -- REV FWD W Cmd-15 LDO
{23} STOP.RUN STOP -- -- -- -- RUN STOP R 527-11 LDI
{24} CMD STP.STRT STOP -- -- -- -- START STOP W Cmd-4 LDO
{25} FREEZE OUT NO -- -- -- -- FREEZE NO R 532-16 LDI
{26} CMD FREEZE FREEZE -- -- -- -- NO FREEZE W Cmd-5 LDO
{27} COAST COAST -- -- -- -- NO COAST R 530-3 LDI
{28} CMD COAST COAST -- -- -- -- NO COAST W Cmd-3 LDO
Common Configuration Points
29 DAY.NIGHT
Note 2
DAY -- -- -- 255 NIGHT DAY W -- Pre-
defined
{30} CURRENT LIM
Note 3
Note 4 A 0.1 0.1 16383 -- -- W 215 LAO
{31} ACCEL TIME 1 Note 4 SEC 1 1 4095 -- -- R/W 206 LAO
{32} DECEL TIME 1 Note 4 SEC 1 1 4095 -- -- R/W 207 LAO

Other manuals for Danfoss VLT 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 and is the answer not in the manual?

Danfoss VLT 6000 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000
CategoryController
LanguageEnglish

Related product manuals