2.1.6 Safe Stop Installation - FC 302 only (and FC 301 in Frame Size A1)
To carry out an installation of a Category 0 Stop (EN60204) in
conformance with Safety Cat. 3 (EN 954-1) / PL “d” (ISO
13849-1), follow these instructions:
1. The bridge (jumper) between Terminal 37 and 24 V DC must be
removed. Cutting or breaking the jumper is not sufficient. Re-
move it entirely to avoid short-circuiting. See jumper on illus-
tration.
2. Connect terminal 37 to 24 V DC by a short circuit-protected ca-
ble. The 24 V DC voltage supply must be interruptible by a Cat.
3 (EN 954-1) / PL “d” (ISO 13849-1) circuit interrupt device. If
the interrupt device and the adjustable frequency drive are
placed in the same installation panel, you can use a regular cable
instead of a protected one.
3. The safe stop function only fulfills Cat. 3 (EN 954-1) / PL “d”
(ISO 13849-1) if particular protection against, or avoidance of,
conductive contamination is provided. Such a protection is ach-
ieved by using FC 302 with protection class IP54 or higher. If
FC 302 with lower protection (or FC 301 A1, which is only de-
livered with an IP21 enclosure) are used, then an operating en-
vironment corresponding to the inside of an IP54 encapsulation
must be ensured. If there is a risk of conductive contamination
in the operating environment, an obvious solution,would be to
mount the devices in a cabinet that provides IP54 protection.
Figure 2.1: Bridge jumper between terminal 37 and 24 VDC
The illustration below shows a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1). The circuit interrupt is caused
by an opening door contact. The illustration also shows how to connect a non-safety-related hardware coast.
Figure 2.2: Figure of the essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) /
PL “d” (ISO 13849-1).
2 Safety Instructions and General Warning
VLT
®
AutomationDrive FC 300 Instruction
Manual
2-8
MG.33.AG.22 - VLT
®
is a registered Danfoss trademark
2

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals