1-20 Motor Power [kW]
Range: Function:
Application
dependent*
[Application dependant] Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. This parameter is visible in LCP if
par. 0-03
Regional Settings
is
International
[0].
NOTE!
Four sizes down, one size up from nominal unit rating.
Application
dependent*
[Application dependant]
1-22 Motor Voltage
Range: Function:
Application
dependent*
[Application dependant] Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Range: Function:
Application
dependent*
[20 - 1000 Hz] Min - Max motor frequency: 20–1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to adapt the load independent settings in par. 1-50
Motor
Magnetization at Zero Speed
to par. 1-53
Model Shift Frequency
. For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High Limit
[RPM]
and par. 3-03
Maximum Reference
to the 87 Hz application.
1-24 Motor Current
Range: Function:
Application
dependent*
[Application dependant] Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
NOTE!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range: Function:
Application
dependent*
[100 - 60000 RPM] Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.