[124] Running reverse Output is high when the adjustable frequency drive is running counter clockwise (the logical product
of the status bits ‘running’ AND ‘reverse’).
[125] Drive in hand mode Output is high when the adjustable frequency drive is in hand on mode (as indicated by the LED
light above [Hand on]).
[126] Drive in auto mode Output is high when the adjustable frequency drive is in hand on mode (as indicated by the LED
light above [Auto on]).
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay
8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[0] * No operation All digital and relay outputs are default set to “No Operation”.
[1] Control ready The control card is ready. For example, Feedback from a drive where the control is supplied by an
external 24 V (MCB107) and the main power to drive is not detected.
[2] Drive ready Drive is ready to operate. Line power and control supplies are OK.
[3] Drive rdy/rem ctrl The adjustable frequency drive is ready for operation and is in auto on mode.
[4] Enable / no warning Ready for operation. No start or stop commands have been applied (start/disable). No warnings are
active.
[5] Running Motor is running, and shaft torque present.
[6] Running / no warning Output speed is higher than the speed set in par. 1-81 Min Speed for Function at Stop [RPM]. The
motor is running and no warnings.
[7] Run in range/no warn Motor is running within the programmed current and speed ranges set in par. 4-50
Warning Current
Low
and par. 4-53
Warning Speed High
. No warnings.
[8] Run on ref/no warn Motor runs at reference speed. No warnings.
[9] Alarm An alarm activates the output. No warnings
[10] Alarm or warning An alarm or a warning activates the output.
[11] At torque limit The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 4-17
Torque Limit Generator
Mode
has been exceeded.
[12] Out of current range The motor current is outside the range set in par. 4-18
Current Limit
.
[13] Below current, low Motor current is lower than set in par. 4-50
Warning Current Low
.
[14] Above current, high Motor current is higher than set in par. 4-51
Warning Current High
.
[15] Out of speed range Output speed/frequency is outside the frequency ranges set in par. 4-52
Warning Speed Low
and
par. 4-53
Warning Speed High
.
[16] Below speed, low Output speed is lower than the setting in par. 4-52
Warning Speed Low
[17] Above speed, high Output speed is higher than the setting in par. 4-53
Warning Speed High
.
[18] Out of feedb. range Feedback is outside the range set in par. 4-56
Warning Feedback Low
and par. 4-57
Warning Feed-
back High
.
[19] Below feedback, low Feedback is below the limit set in par. 4-56
Warning Feedback Low
.
[20] Above feedback, high Feedback is above the limit set in par. 4-57
Warning Feedback High
.
VLT
®
AutomationDrive FC 300 Instruction
Manual
4 How to Program
MG.33.AG.22 - VLT
®
is a registered Danfoss trademark
4-25
4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals