[124] Running reverse Output is high when the adjustable frequency drive is running counter clockwise (the logical product
of the status bits ‘running’ AND ‘reverse’).
[125] Drive in hand mode Output is high when the adjustable frequency drive is in hand on mode (as indicated by the LED
light above [Hand on]).
[126] Drive in auto mode Output is high when the adjustable frequency drive is in hand on mode (as indicated by the LED
light above [Auto on]).
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay
8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[0] * No operation All digital and relay outputs are default set to “No Operation”.
[1] Control ready The control card is ready. For example, Feedback from a drive where the control is supplied by an
external 24 V (MCB107) and the main power to drive is not detected.
[2] Drive ready Drive is ready to operate. Line power and control supplies are OK.
[3] Drive rdy/rem ctrl The adjustable frequency drive is ready for operation and is in auto on mode.
[4] Enable / no warning Ready for operation. No start or stop commands have been applied (start/disable). No warnings are
active.
[5] Running Motor is running, and shaft torque present.
[6] Running / no warning Output speed is higher than the speed set in par. 1-81 Min Speed for Function at Stop [RPM]. The
motor is running and no warnings.
[7] Run in range/no warn Motor is running within the programmed current and speed ranges set in par. 4-50
Warning Current
Low
and par. 4-53
Warning Speed High
. No warnings.
[8] Run on ref/no warn Motor runs at reference speed. No warnings.
[9] Alarm An alarm activates the output. No warnings
[10] Alarm or warning An alarm or a warning activates the output.
[11] At torque limit The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 4-17
Torque Limit Generator
Mode
has been exceeded.
[12] Out of current range The motor current is outside the range set in par. 4-18
Current Limit
.
[13] Below current, low Motor current is lower than set in par. 4-50
Warning Current Low
.
[14] Above current, high Motor current is higher than set in par. 4-51
Warning Current High
.
[15] Out of speed range Output speed/frequency is outside the frequency ranges set in par. 4-52
Warning Speed Low
and
par. 4-53
Warning Speed High
.
[16] Below speed, low Output speed is lower than the setting in par. 4-52
Warning Speed Low
[17] Above speed, high Output speed is higher than the setting in par. 4-53
Warning Speed High
.
[18] Out of feedb. range Feedback is outside the range set in par. 4-56
Warning Feedback Low
and par. 4-57
Warning Feed-
back High
.
[19] Below feedback, low Feedback is below the limit set in par. 4-56
Warning Feedback Low
.
[20] Above feedback, high Feedback is above the limit set in par. 4-57
Warning Feedback High
.