FC 300 Design Guide
How to Program
Function:
When se t to O ff [0], the Digital Potentiometer
reference will be reset to 0% after power-up.
If set to On [1], the last Digital Potentiometer
reference will be restored at power-up.
3-93 Maximum Limit
Range:
0-200%
*
100%
Function:
Set the maximum value that the Digital
Potentiometer reference is allowed to attain. This is
advisable if the Digital Potentiometer is only meant
for fine tuning of the resulting reference.
3-94 Minimu m Limit
Range:
-200 - 200 %
*
-100%
Function:
Set the minimum value that the Digital
Potentiometer reference is allowed to attain. This is
advisable if the Digital Potentiometer is only meant
for fine tuning of the resulting reference.
3-95 Ramp Delay
Range:
0.000 - 3600.00 s
*
1.000s
Function:
Adjust the delay before the adjustable frequency
drive starts to ramp the reference. With a delay
of 0 ms, the reference starts to ramp as soon as
the INCREASE / DEC REASE goes hi gh.
*
default setting ()display text []value for use in communication via serial communication port
162
MG.33.B