How to fix a Danfoss VLT AutomationDrive FC 360 DC Drives motor that is not running?
- DDerek RobinsonAug 31, 2025
If the motor is not running, there might be several causes. First, check if the LCP stop is active and press [Auto On] or [Hand On] to run the motor. Second, ensure a valid start signal is applied. Third, verify that the motor coast signal is not active by applying 24 V on terminal 27 or programming this terminal to No operation. Finally, confirm that the reference signal source is correctly programmed, the wiring is correct, the terminals are scaled properly, and the reference signal is valid.