Transition State Control word Status word Action
Start condition 0000 0000
0
Start-upNot ready to switch on
0000 0200
1
Not ready to switch on Switch on disabled
0000, 0001 0240
2
Switch on disableReady to switched on
0006 0231
3
Ready to switch onSwitched on
0007 0233
4
Switched onOperation enabled
000F 0237
5
Operation enabledSwitched on
0007 0233
Motor ramps to 0 RPM with programmed
ramp-down parameter.
6
Switched onReady to switch on
0006 0231
7
Ready to switch onSwitch on disable
0001, 0000 0240
8
Operation enableReady to switch on
0006 0231
The power section is switched o immediately,
and the motor is free to rotate if unbraked.
9
Operation enableSwitch on disable
0001, 0000 0240
The power section is switched o immediately,
and the motor is free to rotate if unbraked.
10
Switched onSwitched on disable
0001, 0000 0240
The power section is switched o immediately,
and the motor is free to rotate if unbraked.
11
Operation enabledQuick stop active
0002 0207
The motor ramps to 0 RPM with programmed
quick-ramp parameter.
12
Quick stop activSwitch on disabled
0001, 0000 0240
The power section is switched o immediately,
and the motor is free to rotate if unbraked.
13
All statesFault reaction active
xxxx 023F
14
Fault reaction activeFault
xxxx
023F (0238
by InterBus)
15
FaultSwitch on disabled
0000 0240
16
Quick stop activeOperation enable (not
supported)
Table 4.4 DSP 402 State Transitions
Control Programming Guide
MG92G102 Danfoss A/S © 06/2015 All rights reserved. 19
4 4