8.2.8 EMCY Error Code
(OD: 1003)
Code (hex) Description
0 No fault.
1000 General fault.
2130 Short circuit.
2213 Overcurrent during start-up.
2240 Short to ground.
2310 Continuous overcurrent.
2311 Current inside the device.
3100 Mains voltage.
3130 Phase failure.
3210 Overvoltage inside the device.
3220 Undervoltage inside the device.
3300 Output voltage.
4210 Exceed device temperature.
4310 Excess frequency converter temperature.
5110 Low voltage power supply.
5112 +24 V power supply.
5210 Measurement circuit.
6100 Internal software fault.
7110 Brake chopper.
8100 Communication.
8110 CAN overrun (objects lost).
8120 CAN in error (passive mode).
8130 Life Guard error or heartbeat error.
8140 Recovered from Bus O.
8150 Transmit COB-ID collision.
8210 PDO not processed due to length error.
8220 PDO length exceeded.
8302 Torque limiting.
FFxx Vendor specic.
Table 8.9 EMCY Error Code