A trip is the action following an alarm. The trip coasts the
motor and is reset by pressing [Reset] or by a digital input
(parameter group 5-1* Digital Inputs [1]). The origin event
that caused an alarm cannot damage the frequency
converter or cause dangerous conditions. A trip lock is an
action when an alarm occurs, which could damage the
frequency converter or connected parts. A trip lock
situation can only be reset by a power cycling.
Warning yellow
Alarm ashing red
Trip locked yellow and red
Table 7.2 LED Indication
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning
Word 2
Extended
Status Word
Extended
Status Word 2
Alarm Word Extended Status Word
0 00000001 1 Brake Check
(A28)
ServiceTrip,
Read/Write
Brake Check (W28) Start
Delayed
Ramping O
1 00000002 2 Pwr.card temp
(A69)
ServiceTrip,
(reserved)
Pwr.card temp (A69) Stop
Delayed
AMA Running Hand/Auto
2 00000004 4 Ground Fault
(A14)
ServiceTrip,
Typecode/
Sparepart
Ground Fault (W14) reserved Start CW/CCW
start_possible is
active, when the
DI selections [12]
OR [13] are
active and the
requested
direction
matches the
reference sign
Probus OFF1
active
3 00000008 8 Ctrl.Card Temp
(A65)
ServiceTrip,
(reserved)
Ctrl.Card Temp (W65) reserved Slow Down
slow down
command active,
e.g. via CTW bit
11 or DI
Probus OFF2
active
4 00000010 16 Ctrl. Word TO
(A17)
ServiceTrip,
(reserved)
Ctrl. Word TO (W17) Catch Up
catch up
command active,
e.g. via CTW bit
12 or DI
Probus OFF3
active
5 00000020 32 Over Current
(A13)
reserved Over Current (W13) reserved Feedback High
feedback > 4-57
Relay 123 active
6 00000040 64 Torque Limit
(A12)
reserved Torque Limit (W12) reserved Feedback Low
feedback < 4-56
Start Prevented
7 00000080 128 Motor Th Over
(A11)
reserved Motor Th Over (W11) reserved Output Current
High
current > 4-51
Control Ready
8 00000100 256 Motor ETR Over
(A10)
reserved Motor ETR Over
(W10)
reserved Output Current
Low
current < 4-50
Drive Ready
9 00000200 512 Inverter Overld.
(A9)
Discharge
High
Inverter Overld (W9) Discharge
High
Output Freq High
speed > 4-53
Quick Stop
10 00000400 1024 DC under Volt
(A8)
Start Failed DC under Volt (W8) Multi-
motor
underloa
d
Output Freq Low
speed < 4-52
DC Brake
Troubleshooting Operating Instructions
MG34M422 Danfoss A/S © Rev. 2013-07-03 All rights reserved. 151